Chinese Version

CANcheck

 

-Installation tester for CAN networks

CANcheck allows the simple test of CAN networks during commisioning, maintenance and for the search of faults. For this, the battery-operated hand-held device is connected to the CAN network to be tested and operated via a clearly structured menu.

Functions/Features

  • Cable test with network switched off and operational test with network switched on ;
  • Wiring test: test of the resistances between all pins of the CAN-connector (assignment in accordance with CiA), assessment based on pre-defined threshold values;
  • Terminal resistance test: measurement of the resistance between CAN_H and CAN_L;
  • Measurement of the signal level: absolute and differential signal level listed according to identifier;
  • Cable length: measurement of cable length via pulse-time delay;
  • Baud rate measurement: measurement of baud rate of the tested CAN system;
  • Identifier scan: determination of all identifiers transmitted and display of reception frequency;
  • Bus load: measurement of the current bus load of the CAN system;
  • Error frames: number of error frames per time unit;
  • User's guide: test instructions before the test, OK or error message after the test, continuation after acknowledgement;
  • Multilingual: test instructions in German or English;
  • Self-test of the applicance when switched on.

 

 

The CANcheck is operated by means of a simple menu control via cursor keys and LCD display. Test results can be output via the LCD display or a connected PC.

For display of the results on a PC, the CANcheck is connected to the PC via a USB port. Results are displayed on the PC via a terminal program. The logging function of the terminal program enables the test results to be archived in a file or printed out.

Technical Data

Display 128 x 64 pixels; background light can be switched on or off
Keypad Touch-sensitive keypad with 6 keys
Switch on/off Switch on by pressing any key; switches off automatically after 10 mins.
USB port USB 2.0
CAN interface ISO/IS 11898 high-speed CAN
Power Supply 4 x 1.5 V Mignon Battery (AA)
Power consumption 0.5 W
Operating time approx. 24 hrs. with a battery capacity of 2850mAh
Temperature range 0 - +50C
Housing & dimensions sturdy aluminum housing, 116 x 160 x 34 mm (W/H/D)

 

The 10th Floor, Quantum Plaza, No. 27, Zhichun Road, Haidian District, Beijing, 100083, P.R. China
Tel: +86-10-82357579, 82357580, 82357576

Fax: +86-10-82357574

info@mcu-world.com