-Installation
tester for CAN networks
CANcheck
allows the simple test of CAN networks during commisioning, maintenance
and for the search of faults. For this, the battery-operated hand-held
device is connected to the CAN network to be tested and operated via a
clearly structured menu.
 |
Functions/Features
- Cable
test with network switched off and operational test with network
switched on ;
- Wiring
test: test of the resistances between all pins of the CAN-connector
(assignment in accordance with CiA), assessment based on pre-defined
threshold values;
- Terminal
resistance test: measurement of the resistance between CAN_H and
CAN_L;
- Measurement
of the signal level: absolute and differential signal level listed
according to identifier;
- Cable
length: measurement of cable length via pulse-time delay;
- Baud
rate measurement: measurement of baud rate of the tested CAN system;
- Identifier
scan: determination of all identifiers transmitted and display
of reception frequency;
- Bus
load: measurement of the current bus load of the CAN system;
- Error
frames: number of error frames per time unit;
- User's
guide: test instructions before the test, OK or error message
after the test, continuation after acknowledgement;
- Multilingual:
test instructions in German or English;
- Self-test
of the applicance when switched on.
|
The CANcheck is operated by means of a simple menu control via cursor
keys and LCD display. Test results can be output via the LCD display or
a connected PC.
For
display of the results on a PC, the CANcheck is connected to the PC via
a USB port. Results are displayed on the PC via a terminal program. The
logging function of the terminal program enables the test results to be
archived in a file or printed out.
Technical
Data
| Display |
128
x 64 pixels; background light can be switched on or off |
| Keypad |
Touch-sensitive
keypad with 6 keys |
| Switch
on/off |
Switch
on by pressing any key; switches off automatically after 10 mins. |
| USB
port |
USB
2.0 |
| CAN
interface |
ISO/IS
11898 high-speed CAN |
| Power
Supply |
4
x 1.5 V Mignon Battery (AA) |
| Power
consumption |
0.5 W |
| Operating
time |
approx. 24
hrs. with a battery capacity of 2850mAh |
| Temperature
range |
0 - +50C |
| Housing
& dimensions |
sturdy
aluminum housing, 116 x 160 x 34 mm (W/H/D) |
|